The Potter PVE-802 Voice Evacuation Panel is designed to be used with any Potter Fire Alarm Control Panel or UL-864 Listed Fire Alarm Control Panel. The PVE-802 provides automatic and manual fire alarm audio signaling and live voice paging during an emergency situation. The PVE-802 is fully compatible with the Potter’s VAB-802 Audio Booster. The combination of the PVE-802 and VAB-802 meets the total system wattage requirements of virtually any application using the true distributed audio technology.
The PVE-802 Voice Evacuation Panel contains:
Key status indicators viewable on the front panel display include: a green AC power on LED, a yellow amplifier trouble LED, and a yellow power supply trouble LED. Additional diagnostic LEDs that are mounted on the amplifier PCB and on the power supply.
There are 3 toggle switches that provide for manual activation of either Message 1, Message 2, or to initiate an system wide page from the PVE-802 throughout all distributed VAB-802 Audio Boosters.
The built-in, dual programmable, flash based, digital message/tone generator of the PVE-802 Voice Evacuation Panel comes standard with Message 1 programmed for Evacuation and Message 2 programmed for Alert messages. Both messages are field programmable for tailoring to meet specific installation requirements. Digital messages/tones are programmed in a user-friendly tool that users can select from various industry standard messages/tones, such as, leading and trailing tones and male or female voice messages. In addition, personalized wave files (.wav) can be downloaded and added to allow complete customization of messages/tones.
In support of some local requirements, the VAB-802 may be set to a “backup mode” where as a precaution, if primary amplifier fails, the secondary amplifier automatically engages and overrides the primary amplifier, provided there are no short circuits in the field speaker circuit wiring. For project flexibility, each PVE-802 and VAB-802 can be setup to produce their own messages to make setting up a dual channel, three channel, or floor above/floor below application easy.
3530001 Specifications PDF
Product Reviews
Write your own review
Rate this product: